§ 17.18.020. International Mechanical Code—Adopted.  


Latest version.
  • The 2015 International Mechanical Code published by the International Code Council, Inc., a copy of which is on file in the Department of Planning and Zoning, is adopted as the Mechanical Code for the City of Annapolis with the following amendment:

    In Section 603.18 at end of paragraph after "instructions." add the following: "All registers, grills and diffusers installed in suspended ceilings shall be provided with independent suspension to ensure that the register, grill, or diffuser will not drop more than three inches when the framing members no longer provide support. The minimum support wire shall meet or exceed 12# S.W.G. firmly secured to the register, grill, or diffuser and the building structure."

    (Ord. O-34-06 § 1 (part), 2006: Ord. O-28-04 § 1 (part), 2004: Ord. O-38-01 § 1 (part): Ord. O-54-95 § 1 (part): Ord. O-31-91 § 1 (part))

(Ord. No. O-21-10 Amended, § I, 11-8-2010; Ord. No. O-23-12, § I, 7-23-2012; Ord. No. O-12-16 Amended, § I, 5-23-2016; Ord. No. O-50-16 Amended, § I, 2-13-2017)